Home Raceway, Duct, Conduit Cable Tray Systems Cable Trays Fill Capacity and Load Chart
Cable Trays Fill Capacity and Load Chart
CM20 - (.1870)
For pricing and more info, click here
| Tray Size | Fill Area | Max. # Cables* | Approx. Max. Cable Weight** (lbs/ft) | Tested Load Capacity*** (lbs/ft) | |
| 50% fill ratio | |||||
| 5' | 10' | ||||
| (2x6x10) | 13.2 | 60 | 4.29 | 27 | 14 |
| (2x8x10) | 17.6 | 174 | 5.742 | 29 | 16 |
| (2x12x10) | 26.4 | 260 | 8.58 | 34 | 19 |
| (2x18x10) | 39.6 | 394 | 13.002 | 45 | 22 |
| (2x24x10) | 52.8 | 527 | 17.391 | 84 | 33 |
| (4x6x10) | 23.2 | 253 | 8.349 | 35 | 17 |
| (4x8x10) | 33.6 | 331 | 10.923 | 48 | 25 |
| (4x12x10) | 50.4 | 496 | 16.368 | 6 | 28 |
| (4x18x10) | 75.6 | 751 | 24.783 | 71 | 25 |
| (4x24x10) | 100.8 | 998 | 32.934 | 93 | 28 |
CM10 - (.1200)
For pricing and more info, click here
| Tray Size | Fill Area | Max. # Cables* | Approx. Max. Cable Weight** (lbs/ft) | Tested Load Capacity*** (lbs/ft) | |
| 50% fill ratio | |||||
| 5' | 10' | ||||
| (2x2x10) | 4.4 | 44 | 1.452 | 25 | 15 |
| (2x4x10) | 8.8 | 86 | 2.838 | 17 | 14 |
| (2x6x10) | 13.2 | 130 | 4.29 | 20 | 10 |
| (2x8x10) | 17.6 | 174 | 5.742 | 25 | 12 |
| (2x12x10) | 26.4 | 260 | 8.58 | 31 | 16 |
| (4x2x10) | 8.4 | 84 | 2.772 | 25 | 13 |
| (4x4x10) | 25.2 | 252 | 5.544 | 27 | 15 |
| (4x6x10) | 33.6 | 336 | 11.088 | 41 | 20 |
| (4x8x10) | 50.4 | 504 | 16.362 | 55 | 31 |
| (4x12x10) | 12.4 | 124 | 4.092 | 33 | 16 |
* Chart is based on 50% fill of 4 UTP Category 6 cable (O.D.=.21 .033lbs/ft)
** Not maximum loading weight for the tray; practical guide on the amount of cable weight that can be installed
*** Tested in accordance with NEMA VE-1/CSA E222.2 #126.1
Facebook Comments