Wiremold FlameStopper Thru-Wall and Thru-Floor Fittings
Maintain a 3 or 4 Hour Fire Rating Between Walls and Rooms
![]()
Close Window
Wiremold FlameStopper Fittings
This requires one or more of the following: javascript enabled, Flash Video Player, and Quicktime or Windows Media Player
|
With a passive fire rating of up to four hours between walls and three hours between floors, the Wiremold FlameStopper is a perfect complement to any existing sprinkler system. Designed to provide an excellent barrier for new or existing construction, it’s great for owners, tenants and inspection authorities alike. |
- Mechanical doors can be closed to provide a barrier between rooms prior to cabling installation
- Adding or subtracting cables is easy: just adjust the doors to accommodate more or fewer cables - no need to adjust the intumescent material
- Fittings are shipped in pairs, and installed on both sides of the wall or floor to accommodate any thickness
- 4-hour fire and temperature rating ensures that the FlameStopper will maintain the integrity of fire rated walls or floors
- Retrofit kits available; no need to plug existing construction with caulks, sealants or putties
- Kits consist of:
- Split conduit for installations where no conduit is installed
- Large firestop wall plate for irregular hole penetrations
- Heat shield for existing extended conduit lengths
- ASTM E814, UL1479, UL2043
| Flame: The F Rating (F and FH in Canada) is expressed in hours. This number indicates the specific length of time that a barrier can withstand fire before being consumed or before permitting the passage of flame through the opening. |
||||
| Temperature: The T Rating (FT and FTH in Canada) is expressed in hours. This number indicates the length of time that the temperature on the non-fire side of the penetration does not exceed 325 degrees F above the ambient temperature. | ||||
| Air Leakage: The L Rating is expressed in CFM. This number indicates the amount of air (or cold smoke) that can leak through a penetration. | ||||
| THROUGH-WALL RATINGS FOR FS2R & FS4R SERIES (When used alone for new construction or existing construction with heat shield.) | ||||
| UL RATINGS (US Ratings) | MAX. RATING | UL RATINGS (Canadian Ratings) | MAX. RATING | |
| F Rating w/ & w/o cables | 4 Hours | F & FH Rating w/ & w/o cables | 4 Hours | |
| T Rating w/coax cable | 4 Hours | FT & FTH Rating w/coax cable | 4 Hours | |
| T Rating w/fiber optic cable | 4 Hours | FT & FTH Rating w/fiber optic cable | 4 Hours | |
| T Rating w/Max. 1" fiber optic rcwy. w/fiber optic fill | 4 Hours | FT & FTH Rating w/Max. 1" fiber optic rcwy. w/fiber optic fill | 4 Hours | |
| T Rating w/Max. 4-pair cable (22 ga & smaller) | 3 Hours | FT & FTH Rating w/Max. 4-pair cable (22 ga & smaller) | 3 Hours | |
| T Rating w/Max. 4 conductor (2AWG & smaller) | 1 Hours | FT & FTH Rating w/Max. 4 conductor (2AWG & smaller) | 1 Hours | |
| T Rating w/Max. 100-pair cable (24 ga & smaller) | 1 Hours | FT & FTH Rating w/Max. 100-pair cable (24 ga & smaller) | 1 Hours | |
| T Rating w/Max. 400-pair cable (24 ga & smaller) | 45 Minutes | FT & FTH Rating w/Max. 400-pair cable (24 ga & smaller) | 45 Minutes | |
| T Rating w/MC cable (8 wire max. 12 ga & smaller) | 15 Minutes | FT & FTH Rating w/MC cable (8 wire max. 12 ga & smaller) | 15 Minutes | |
| L Rating at ambient w/o cables (doors closed) | 2.6 cfm | L Rating at ambient w/o cables (doors closed) | 2.6 cfm | |
| L Rating at 400°F w/o cables (doors closed) | 1.9 cfm | L Rating at 400°F w/o cables (doors closed) | 1.9 cfm | |
| L Rating at ambient with cables | 2.8 cfm | L Rating at ambient with cables | 2.8 cfm | |
| L Rating at 400°F with cables | 1.3 cfm | L Rating at 400°F with cables | 1.3 cfm | |
| Suitable for use in air handling spaces (plenums) | Yes | Suitable for use in air handling spaces (plenums) | Yes | |
| THROUGH-WALL RATINGS FOR FS2R & FS4R SERIES (When used with wall plate for retrofit applications.) | ||||
| UL RATINGS (US Ratings) | MAX. RATING | UL RATINGS (US Ratings) | MAX. RATING | |
| F Rating w/ & w/o cables | 2 Hours | F & FH Rating w/ & w/o cables | 2 Hours | |
| T Rating w/Max. 4-pair cable (22 ga & smaller) | 1.25 Hours | FT & FTH Rating w/Max. 4-pair cable (22 ga & smaller) | 1.25 Hours | |
| T Rating w/coax cable | 1 Hour | FT & FTH Rating w/coax cable | 1 Hour | |
| T Rating w/fiber optic cable | 1.25 Hours | FT & FTH Rating w/fiber optic cable | 1.25 Hours | |
| T Rating w/Max. 1" fiber optic rcwy. w/fiber optic fill | 1.25 Hours | FT & FTH Rating w/Max. 1" fiber optic rcwy. w/fiber optic fill | 1.25 Hours | |
| T Rating w/MC cable (8 wire max. 12 ga & smaller) | 15 Minutes | FT & FTH Rating w/MC cable (8 wire max. 12 ga & smaller) | 15 Minutes | |
| L Rating at ambient w/o cables (doors closed) | 1.7 cfm | L Rating at ambient w/o cables (doors closed) | 1.7 cfm | |
| L Rating at 400°F w/o cables (doors closed) | 1.8 cfm | L Rating at 400°F w/o cables (doors closed) | 1.8 cfm | |
| L Rating at ambient with cables | 3.3 cfm | L Rating at ambient with cables | 3.3 cfm | |
| L Rating at 400°F with cables | 2.0 cfm | L Rating at 400°F with cables | 2.0 cfm | |
| Suitable for use in air handling spaces (plenums) | Yes | Suitable for use in air handling spaces (plenums) | Yes | |
| THROUGH-FLOOR RATINGS FOR FS2R & FS4R SERIES (When used alone.) | ||||
| UL RATINGS (US Ratings) | MAX. RATING | UL RATINGS (Canadian Ratings) | MAX. RATING | |
| F Rating w/ & w/o cables | 3 Hours | F Rating w/ & w/o cables | 3 Hours | |
| T Rating w/o cables | 3 Hours | T Rating w/o cables | 3 Hours | |
| T Rating w/coax cable | 3 Hours | T Rating w/coax cable | 3 Hours | |
| T Rating w/fiber optic cable | 3 Hours | T Rating w/fiber optic cable | 3 Hours | |
| T Rating w/Max. 4-pair cables (22 ga. or smaller) | 3 Hours | T Rating w/Max. 4-pair cables (22 ga. or smaller) | 3 Hours | |
| T Rating w/Max. 4-conductor (2 ga. or smaller) | 45 Minutes | T Rating w/Max. 4-conductor (2 ga. or smaller) | 45 Minutes | |
| T Rating w/Max. 100-pair cables (24 ga. or smaller) | 1 Hour | T Rating w/Max. 100-pair cables (24 ga. or smaller) | 1 Hour | |
| T Rating w/Max. 400-pair cables (24 ga. or smaller) | 45 Minutes | T Rating w/Max. 400-pair cables (24 ga. or smaller) | 45 Minutes | |
| T Rating w/MC cable (8 wire Max. 12 ga. or smaller) | 15 Minutes | T Rating w/MC cable (8 wire Max. 12 ga. or smaller) | 15 Minutes | |
| L Rating at ambient w/o cables (doors closed) | 2.6 cfm | L Rating at ambient w/o cables (doors closed) | 2.6 cfm | |
| L Rating at 400°F w/o cables (doors closed) | 1.9 cfm | L Rating at 400°F w/o cables (doors closed) | 1.9 cfm | |
| L Rating at ambient with cables | 2.8 cfm | L Rating at ambient with cables | 2.8 cfm | |
| L Rating at 400°F with cables | 1.3 cfm | L Rating at 400°F with cables | 1.3 cfm | |
| Suitable for use in air handling spaces (plenums) | Yes | Suitable for use in air handling spaces (plenums) | Yes | |
| NOTE: Minimum 4 1/2" [114mm] thick reinforced lightweight or normal weight (100-150 pcf) [1600-2400 kg/m3] concrete floor. Maximum diameter of opening is 4 1/2" [114mm]. | ||||
Wire Fill Capacity Charts for FlameStopper
| Data/Communication Wire | |||||||
| Cable/Wire Size | O.D. | FS2 (Fill) | FS4 (Fill) | ||||
| inches | (mm) | 40% | 60% | 40% | 60% | ||
| Unshielded Twisted Pair | 4-pair, 24 AWG Cat 3 UTP | 0.19 | [4.8] | 47 | 71 | 208 | 312 |
| 4-pair, 24 AWG Cat. 5e UTP | 0.21 | [5.3] | 38 | 58 | 170 | 255 | |
| 4-pair, 24 AWG Cat. 6 UTP | 0.25 | [6.3] | 20 | 30 | 68 | 100 | |
| Telephone | 2-pair, 24 AWG | 0.14 | [3.6] | 87 | 130 | 383 | 574 |
| 25-pair, 24 AWG | 0.41 | [10.4] | 10 | 15 | 44 | 67 | |
| 50-pair, 24 AWG | 0.58 | [14.7] | 5 | 7 | 22 | 33 | |
| 100-pair, 24 AWG | 0.7 | [17.8] | 3 | 5 | 15 | 22 | |
| 400-pair, 24 AWG | 1.47 | [37.3] | 0 | 1 | 3 | 5 | |
| Coaxial | RG58/U | 0.195 | [5.0] | 45 | 67 | 197 | 296 |
| RG59/U | 0.242 | [6.1] | 29 | 43 | 128 | 192 | |
| RG62/U | 0.242 | [6.1] | 29 | 43 | 128 | 192 | |
| RG6/U | 0.27 | [6.9] | 21 | 32 | 95 | 140 | |
| Fiber Optic | 2 Count | 0.18 | [4.6] | 52 | 79 | 231 | 347 |
| 6 Count | 0.21 | [5.3] | 38 | 58 | 170 | 255 | |
| 24 Count | 0.4 | [10.2] | 10 | 16 | 46 | 70 | |
| 48 Count | 0.45 | [11.4] | 8 | 12 | 37 | 55 | |
| 96 Count | 0.56 | [14.2] | 5 | 8 | 23 | 35 | |
| Power Wiring | |||||||
| Cable Type | O.D. | FS2 (Fill) | FS4 (Fill) | ||||
| inches | (mm) | 40% | 60% | 40% | 60% | ||
| Max 4 cond. No. 2 AWG (or smaller) copper conductor cable with XLPE/PVX insulation and PVC jacket | 0.375 | [9.5] | 12 | 18 | 53 | 80 | |
| 0.500 | [12.7] | 6 | 10 | 30 | 45 | ||
| 0.625 | [15.9] | 4 | 6 | 19 | 28 | ||
| 0.750 | [19.1] | 3 | 4 | 13 | 20 | ||
| 0.875 | [22.2] | 2 | 3 | 9 | 14 | ||
| 1.000 | [25.4] | 1 | 2 | 7 | 11 | ||
| 1.125 | [28.6] | 1 | 2 | 5 | 8 | ||
| Max 8 cond. No.12 AWG MC (Metal Clad) Cable | 0.375 | [9.5] | 12 | 18 | 53 | 80 | |
| 0.500 | [12.7] | 6 | 10 | 30 | 45 | ||
| 0.625 | [15.9] | 4 | 6 | 19 | 28 | ||
| 0.655 | [16.6] | 3 | 5 | 17 | 26 | ||
| PART # | DESCRIPTION | COLOR | WEIGHT | PRICE |
| WM-SPMGL | FlameStopper, Ground Lug, 5 pack | N/A | 0.06 lb | |
| FlameStopper Trade EMT Conduit Fitting | ||||
| WM-FS2R-RED | 2" Trade EMT Conduit Fitting, for transitioning cables through the fire rated walls/floors for both new and retrofit | Red Finish | 3 lbs | |
| WM-FS4R-RED | 4" Trade EMT Conduit Fitting, for transitioning cables through the fire rated walls/floors for both new and retrofit | Red Finish | 6 lbs | |
| WM-FS2R-GA | 2" Trade EMT Conduit Fitting, for transitioning cables through the fire rated walls/floors for both new and retrofit | Galvanized Finish | 3 lbs | |
| WM-FS4R-GA | 4" Trade EMT Conduit Fitting, for transitioning cables through the fire rated walls/floors for both new and retrofit | Galvanized Finish | 6 lbs | |
| FlameStopper Precut to 7-5/8" Conduit | ||||
| WM-FSPCC2758 | 2" Diameter, Trade Size EMT, fits 6" wall thickness with a 2-hour fire rating | Galvanized Finish | 1 lb | |
| WM-FSPCC4758 | 4" Diameter, Trade Size EMT, fits 6" wall thickness with a 2-hour fire rating | Galvanized Finish | 2.4 lbs | |
| FlameStopper Heat Shield | ||||
| WM-FS2RHS | To use with 2" size conduit when an existing installed conduit extends more than 1" to 6" beyond wall surface | Galvanized Finish | 2.08 lbs | |
| WM-FS4RHS | To use with 4" size conduit when an existing installed conduit extends more than 1" to 6" beyond wall surface | Galvanized Finish | 3 lbs | |
| FlameStopper Retrofit Kit | ||||
| WM-FS2RWP8 | Kit includes; 2" diameter split conduit to enclose existing cables and 8x8 wall plate, for use with WM-FS2R series firestop | Galvanized Finish | 6.2 lbs | |
| WM-FS4RWP12 | Kit includes; 4" diameter split conduit to enclose existing cables and 12x12 wall plate, for use with WM-FS4R series firestop | Galvanized Finish | 12.8 lbs | |