PPanduit Corporation DP5e & DP6 Plus Patch Panel
INSTALLATION INSTRUCTIONS

This section will help you install your Panduit Patch Panel. Follow these instructions for installation of Panduit Fiber Patch Panel model # DP5e and DP6 Plus.

step 1 in installation
step 2 in installation

1. Install the label on the back of the panel in between the rows of connectors. Be sure to install the label with the proper wiring color code facing out and ensure that the port numbers on the label correspond to the port numbers on the panel front.

 

2. Remove 1" (25.4mm) of cable jacket. (Caution: Do not damage conductors.)
Fan out all four twisted pairs in the specified wiring sequence

step 3 in installation
step 4 in installation

3. Lay conductors into the punch down slots in the specified wiring sequence. Cable jacket removal should be minimized to the extent possible. Conductor untwist should be within 1/2" (12.7mm) of termination. For best performance when terminating cable on connecting hardware, the cable pair twists should be maintained as close as possible to the point of termination.

4. DO NOT USE 110 STYLE BLADE FOR PUNCHDOWN
Punch down the conductors using a punch down tool on HIGH setting. ALIGN TOOL WITH BLOCK.
Prior to dressing cable, snap retention caps on as shown above. For DP12688TP ONLY: After termination is complete, install on 89D bracket.