Home > Networking > Wall Plates > Ground Fault Circuit Interrupter Receptacles > Specifications for GFCI Receptacles
GFCI Specifications & Dimensions
Click to go to GFCI Receptacle Main Page
|
|||||||||||||||||||||||
Electrical Specifications | |
| ANSI/NEMA | 5-15R, 5-20R, WD-6 |
| Dielectric Voltage Withstands | 1500V per UL498 |
| Current Interrupting | 10KA/6KV |
| Temperature Rise Max | 30C after 50 cycles OL at 150 pct rated current |
Mechanical Specifications | |
| Terminal ID Brass-Hot, Green Ground, White Neutral Terminal Accommodation | 14-1 2 AWG |
| Product ID Ratings are permanently marked on device | |
Material Specifications | |
| Face Material | Polycarbonate |
| Body Material | Polycarbonate |
| Line Contacts | Brass Double-Wipe 0.031 Thick |
| Terminal Screws | Brass 8-32 |
| Grounding Screws | Brass 8-32 |
| Strap | Zinc-Plated Steel 0.050 thick |
| Clamps | Zinc-Plated Steel |
| Ground Clip | Brass |
| Internal Switch Contacts | Silver and Tin Alloy |
| Available Colors | White or Ivory |
Environmental Specifications | |
| Flammability Rated | V-2 per UL94 |
| Operating Temperature | -35° C to 65° C |
Performance Data | |
| Trip Level | 5mA ± 1mA |
AC Horsepower Ratings | |
| At Rated Voltage | 1-1/2 HP |
The end-of-life intellectual monitoring function | |
| |
Standards and Certifications | |
| |