Home Raceway, Duct, Conduit Cable Tray Systems M.E.2 Cable Tray System M.E.2 Cable Tray Fill Capacity and Load Chart
M.E.2 Cable Tray Fill Capacity and Load Chart
| Tray Size D" x W" x L' |
Tray Weight | Max. # Cables @ 50% fill ratio* |
Load Capacity Over a 5' Span (lbs/ft) |
Load Capacity Over a 10' Span (lbs/ft) |
| 50% Fill Ratio | ||||
| 2x6x7 | 6.94 | 130 | 27 | 14 |
| 2x8x7 | 7.91 | 174 | 29 | 16 |
| 2x12x7 | 9.85 | 260 | 34 | 19 |
| 2x18x7 | 12.83 | 394 | 43 | 22 |
| 2x24x7 | 15.74 | 527 | 52 | 23 |
| 2x6x10 | 9.92 | 130 | 27 | 14 |
| 2x8x10 | 11.12 | 174 | 29 | 16 |
| 2x12x10 | 14.13 | 260 | 34 | 19 |
| 2x18x10 | 18.33 | 394 | 43 | 22 |
| 2x24x10 | 22.48 | 527 | 52 | 23 |
| 4x6x7 | 7.59 | 253 | 35 | 17 |
| 4x8x7 | 8.6 | 331 | 48 | 25 |
| 4x12x7 | 10.57 | 496 | 52 | 28 |
| 4x18x7 | 13.52 | 751 | 68 | 31 |
| 4x24x7 | 16.41 | 998 | 69 | 36 |
| 4x6x10 | 10.84 | 253 | 35 | 17 |
| 4x8x10 | 12.28 | 331 | 48 | 25 |
| 4x12x10 | 16 | 496 | 52 | 28 |
| 4x18x10 | 19.31 | 751 | 68 | 31 |
| 4x24x10 | 23.45 | 998 | 69 | 36 |
*Chart is based on 50% fill of 4 UTP Category 6 cable (O.D. + .21 .033 lbs./ft)
** Not Maximum loading weight for the tray, practical guide on amount of cable weight that can be installed
*** Tested in accordance with NEMA VE-1/CSA E222.2 #126.1