Abesco CP310 FR Acrylic Intumescent Caulk
Technical Data Sheet

Application |Specifications |Testing & Performance Data | First Aid Measures
Exposure Controls/Personal Protection | Handling & Storage | Stability & Reactivity | Regulatory Information

Back to the Main Page

  Product Description

Abesco CP310 is a water based acrylic intumescent caulk which expands and forms an insulating char when exposed to fire or extreme heat. CP310 FR Acrylic Intumescent Caulk is easy to use and has excellent adhesion properties when used with most common building materials. It can be installed using a standard caulking gun (standard cartridge, 20 oz sausage, or bulk filled), pneumatic pumping equipment, or easily applied using a knife or trowel. CP310 does not contain any solvents, PCB’s or asbestos, making it safe to use and environmentally friendly. Cleaning up is easy using just water, with no special handling requirements.

CP 310 FEATURES:

  • Easy installation – saves labor cost
  • Intumescent – expands in a fire to seal around services
  • Halogen Free
  • Paintable when dry (after inspection)
  • UL Classified – complies with Building Codes

 

  Application

CP310 FR Acrylic Intumescent Caulk is used to seal gaps in construction and through-penetrations against the passage of fire, smoke and gases. CP310 has been tested where services penetrate through concrete walls and floors, and drywall constructions, and is suitable for use around copper and steel pipes, steel conduits, electrical cables, data and telephone cables, PVC and CPVC pipes (up to 2" diameter), HVAC ducts, and is also used with other Abesco products such as Z240 Pipe Collars and Series 2 Pipe Wraps.

 

  Specifications

All installations shall be in strict accordance with manufacturers printed instructions. The firestopping caulk shall be a one part water based acrylic intumescent sealant, and shall be tested in accordance with ASTM E814 (UL1479) and classified by Underwriters Laboratories Inc for up to 2 Hour rating.

All through penetrations shall be sealed with a UL Classified system or device as listed within the current UL Fire Resistance Directory, or have approved shop drawings prior to installation. Suitability for a particular application should be determined prior to installation.

 

  Testing & Performance Data

Tested in Accordance with ASTM E814, UL1479
UL Classified 1 and 2 Hour rating
Please visit the UL website for details on our current system

UL ClassifiedFILL VOID OR CAVITY MATERIALS FOR USE IN THROUGH PENETRATION FIRESTOP SYSTEMS SEE UL DIRECTORY OF PRODUCTS CERTIFIED FOR CANADA AND UL FIRE RESISTANCE DIRECTORY 24KP

 

  First Aid Measures

If Inhaled Remove to fresh air. No emergency care anticipated.
If on Skin Wash skin thoroughly with soap and water or a recognized skin cleaner. Do not use solvent or thinners.
If in Eyes Contact lenses should be removed. Irrigate copiously with clean fresh water for at least 10 minutes, holding eyelids apart, and seek medical advice.
If Swallowed If accidentally swallowed, wash mouth with water and give water to drink. Do not induce vomiting.

 

  Exposure Controls / Personal Protection

Ventilation General (natural or mechanically induced fresh air movements)
Eye Protection Eye protection designed to protect against liquid splashes should be worn
Skin Protection Cotton or cotton/synthetic overalls are normally suitable. Grossly contaminated clothing should be removed and the skin washed with soap and water. Cloth gloves are suitable.
Respiratory Protection None normally required

 

  Handling and Storage

Usage Precautions Avoid contact with skin and eyes. Smoking, eating, and drinking should be prohibited in areas of storage and use. Keep containers closed when not in use. Never use high pressure to empty - the container is not a pressure vessel. Ensure good housekeeping and regular safe removal of waste materials.
Storage Precautions Observe label precautions. Store between 40 F and 75 F in a dry, well-ventilated place away from sources of heat. Protect from frost. Keep out of reach of children. Store separately from oxidizing and strongly alkaline and strongly acidic materials.

 

  Stability and Reactivity

Stability Stable under the recommended storage and handling conditions
Conditions to Avoid None
Incompatibility None known
Hazardous Decomposition In a fire, hazardous decomposition products such as smoke, carbon dioxide, and oxides of nitrogen may be produced. Keep away from oxidizing agents and strongly alkaline and strongly acidic materials to prevent the possibility of an exothermic reaction

 

  Regulatory Information

Hazard Communication The product is considered to be an "article" as defined in the federal OSHA Hazard Communication Standard.
DOT Shipping Name Not regulated
Air (IATA) Shipping Not regulated
Ocean (IMDG) Shipping Not regulated
TSCA Inventory Status Chemical components listed on TSCA inventory
SARA Title III, Section 313 This product is classified as an "article" and is not subject to reporting under Section 313 or SARA Title III.

 

 


Currency
Converter


Shop with Confidence